Product:
Fan
Centrifugal Fan
Constructions:
Blower Eurovent : TFEb Series
Drive | : | Belt Drive |
Pressure | : | Hight |
Impeller | : | Forward Curve |
St. Pressure | : | 122 - 1700 mmH2O |
Impeller Dia | : | 350 - 1000 mm. |
Air flow | : | 2 - 60 cmm. |
Spark proof construction:
when explosive fluids are carried or when the plant is installed in dangerous environments, the parts that come into contact with the intaken fluid are constructed by material without iron content to avoid rubbing, motor on request is supplied in special construction.
Corosionproofing construction:
when corrosive fluids are carried, the parts that come into contact with the fluid are painted with special paints or they are constructed with special materials as austentic stainless steels (AISI 304-316 etc.). Constructions can be effected according to the customer’s particular needs.
Usage:
● Also for the suction of very dusty air.
● The fans of this series are particularly suitable for pneumatic conveyances, in cement factories, in the air feeding of the cupolas, in foundries and in oil burners, in mills, in “pasta” factories, in chemical, metallurgical and iron industries where small capacities with medium and high pressures are required.
● The temperature of the fluid sucked in must not exceed 80°C without cooling fan and 150°C with cooling fan.
● The fan is not revolvable
● The fans of this series are particularly suitable for pneumatic conveyances, in cement factories, in the air feeding of the cupolas, in foundries and in oil burners, in mills, in “pasta” factories, in chemical, metallurgical and iron industries where small capacities with medium and high pressures are required.
● The temperature of the fluid sucked in must not exceed 80°C without cooling fan and 150°C with cooling fan.
Blower Eurovent : TFEb Series
Item | Model | HP | Poles | Air Volume | Pressure | Inlet (D) mm. |
Outlet (axb) mm. |
|
cmm | cfm | mmWg | ||||||
1 | FanBlower TFEb 351 | 1/4 - 2 | 2 | 2 - 17 | 70 - 600 | 122 - 695 | 145 | 90x63 |
2 | FanBlower TFEb 401 | 1/3 - 2 | 2 | 2 - 20 | 70 - 700 | 179 - 800 | 145 | 90x63 |
3 | FanBlower TFEb 451 | 1/2 - 3 | 2 | 2 - 25 | 70 - 885 | 158 - 968 | 145 | 90x63 |
4 | FanBlower TFEb 501 | 1/2 - 3 | 2 | 2 - 25 | 70 - 885 | 195 - 990 | 145 | 90x63 |
5 | FanBlower TFEb 561 | 3/4 - 4 | 2 | 2 - 20 | 70 - 700 | 275 - 1,290 | 165 | 100x71 |
6 | FanBlower TFEb 631 | 1 - 5 | 2 | 3 - 25 | 106 - 885 | 335 - 1,300 | 165 | 100x71 |
7 | FanBlower TFEb 711 | 1 - 10 | 2 | 4 - 27 | 141 - 950 | 545 - 1,590 | 165 | 100x71 |
8 | FanBlower TFEb 801 | 5-15 | 4 | 9 - 32 | 318 - 1,131 | 550 - 1,500 | 165 | 100x71 |
9 | FanBlower TFEb 901 | 5-20 | 4 | 8 - 40 | 283 - 1,413 | 700 - 1,600 | 185 | 112x80 |
10 | FanBlower TFEb 1001 | 7.5-40 | 4 | 18 - 60 | 636 - 2,120 | 700 - 1,700 | 229 | 180x125 |
● The fan is not revolvable
ติดตาม Eurovent Blower
Eurovent Blower มี LINE OFFICIAL ACCOUNT แล้วนะ
ติดตามเรื่องราวดีๆแบบอินเทรนด์ ได้ทุกวันผ่าน LINE ID @euroventblower
Product Spec
Drive:
Belt
Pressure:
High
Impeller:
Forward